• Any Questions? Call Us: 91 33 2231 8646
  • Skype: Rieindia
Get social with us!

M8 Power Analyzer

.


M8 Power Analyzer

Salient Features
  • State of art microcontroller based design.
  • 3 line 4 digit ultra bright led display
  • Site programmable ct ratio ( primary & secondary)
  • Site programmable pt ratio ( primary & secondary)
  • True RMS measurement
  • Password protection
  • Total harmonic distortion
  • Auto ranging
  • Universal aux. Supply
Technical Specifications
Aux. Supply       90-270 V AC/DC
Input 3 phase 4 wire
Volts Range 10-500V
Amps .015 to 6.00 Amp
Burden .2 VA max. Per unit for voltage & current signals 3 VA max. On aux supply
Display 3 line * 4 digit
Computation True RMS
Frequency 45 Hz – 65 Hz.
Ambient – 10 to 55 c
Storage -20 to 75 c
Humidity < 95% non- condensing
Dimensions 96*96*55 mom ( L* W* D)
Panel cutout (90)MM * (90)MM
Mounting Flush mounting with side clamps.
Parameters
Volts

RY (phase – phase), YB (phase – phase), BR ( phase – phase), RN ( phase – neutral), YN ( phase – neutral), BN ( phase – neutral)

Amps

R phase, Y phase, B phase

Power factor

R phase, Y phase, B phase

Active power (kw)

R phase, Y phase, B phase

Apparent power (kva)

R phase, Y phase, B phase

Reactive power (kvar)

R phase, Y phase, B phase

Frequency -
Measurement Range
Volts 10-500 VAC L-L
Amps .015A – 6.00 Amp AC
Display update 1 sec
Hz 45.0 to 65.0 Hz
Resolution .1 for Energy , auto ranging for other parameters
Accuracy .5 % of full scale for voltage , current power , power factor
Frequency .1% for Hz
Energy class 1.0